1. Working pressure: 0.3- 1Mpa
2. Ideal working pressure: 0.1.-0.5Mpa
3. Cold water supply temperature range: 5-29 Celsius degree
4. Hot water supply temperature range: 50-80 Celsius degree
5. Setting range: 35--45 OR 35--55 Celsius degree
6. Rated flow: 0.7Cb.m./H(Same as 11.67L/Min)
7. Type: BXHS-15-I
8. Cold water supply failure test: If the cold water supply fails, the volume of outlet water collected during the first 5±0.5s shall be less than 200ml and the temperature of outlet water shall be less than 49 Celsius degree.
If the volume of water collected during the first five seconds ≥200ml, the outlet temperature shall not exceed 42 Celsius degree, the volume of water collected during the second collection period of 30±0.5s shall be less than 300ml.
The temperature of the water outlet shall be at 38±2 Celsius degree after restoration of the cold water supply.
Notes :
We can supply different size of TMVs including DN15 (Nominal Diameter), DN20, DN25, DN32, DN40, DN50, DN80 with different. We are willing to satisfy all your requirements. The valves are not only designed domestic use but also for public use.
As a special manufacturer, 100 percent factory inspection is our effective means to control product quality.
Point of use mixing for wash hand basins, bidets, baths and showers in hospitals, schools, sport and leisure facilities, prisons and other public buildings.
A Thermostatic Mixing Valve is a valve that blends hot water (stored at temperatures high enough to kill bacteria) with cold water to ensure constant, safe outlet temperatures preventing scalding.
They also shut-off rapidly in the event of a hot or cold supply failure to prevent scalding or thermal shock.